GVR Recloser/GVS Kits

The father of modern switchgear, Hawker Siddeley Switchgear Ltd’s world renowned GVR Recloser was the first in a range of equipment utilising one of the most advanced operating mechanism available on the market today – Hawker Siddeley Switchgear Ltd’s Fit and Forget Technology, featuring the award winning magnetic actuator.

Features

The GVR provides ‘intelligent control’ and protection on power distribution networks, whilst offering a lifetime of trouble-free service.

  • Superior, proven Fit & Forget technology with minimal maintenance
  • The Hawker Siddeley Switchgear Ltd patented, single coil magnetic actuator mechanism allows the GVR to operate independently of the MV supply
  • Environmentally friendly vacuum interruption produces no by-products
  • The lightweight, corrosion resistant aluminium tank makes the GVR easier to transport and install
  • The EPDM or silicone bushings are tested for tracking and erosion to IEC 61109 and are resistant to damage from vandalism or mishandling
  • Endurance tested to 10,000 operations
  • Pole mounted or substation mounted, the GVR can be integrated into the most advanced distribution automation schemes, or can operate as a stand-alone recloser
  • By using the advanced control and protection functions of the Panacea, the GVR can also be used in applications where reclosers have not traditionally been used such as closed rings and underfrequency load shedding schemes
  • The 3-in-1 Recloser – the GVR can be configured to function as a Switch, Sectionaliser or Recloser by using one of the specially pre-engineered protection and control cubicles

The GVR automatic recloser is now available as a tank only option for those customers who wish to connect their own protection and control cubicles. Alternatively, customers looking for a ground-mounted solution can select our epoxy separable bushings for cable connected networks.

For Spares, Service and Repair, please click here.

Ratings

 

 

GVR 15

GVR 27

GVR 38

Maximum System Voltage

kV

15.5

27

38

Continuous Current

A

630

630

630

Interrupting Current

kA

12.5 / 16

12.5

10

Impulse Voltage Withstand

kV peak

110

125 / 150

150 (Internal) 170 (External)

Power Frequency Withstand Dry

kVrms for 60 secs

50

60

70

Power Frequency Withstand Wet

kVrms for 60 secs

50

50

60

Rated Gas Pressure for Above

 

Atmospheric

Atmospheric / 0.3 bar*

0.3 bar* gauge

Number of Operations with no maintenance

 

10,000

10,000

10,000

Weight

Kg

145

145 / 155*

155

*Ratings for 150kV impulse version 
 

Standards

General - ANSI C37.60
Electromagnetic - IEC 801
Protection - IEC 255

Applications

The GVR / GVS has a wide range of applications:

  • Pole mounted applications
  • Substation applications
  • Wind Farm applications
  • Switch applications (Auto-reclosing)
  • Sectionaliser applications